–54–
*
64 NORMAL TEST REPORT CODE |
This is sent periodically to test that the communicator and phone lines
are operational (frequency of report is selected in field *49).
RESTORE
REPORT CODES
(
*
69–
*
74)
*
69 GROUP RESTORES FOR TROUBLE, BYPASS
Enter 0 for no (report for each restore), or 1 for yes (report after all
zones restored). Default is “0”. Note: "1" not applicable to Contact ID
reporting.
*
70 ALARM RESTORE REPORT CODE, 1st DIGIT
This is sent when a zone alarm has been restored. The 2nd digit is
automatically sent as the 2nd digit of the zone alarm report code
programmed in field
*56
, if expanded or 4+2 reporting is selected.
*
71 TROUBLE RESTORE REPORT CODE |
This is sent when a trouble in a zone is restored. Field
*
69 applies.
*
72 BYPASS RESTORE REPORT CODE |
This is sent when a zone that has been bypassed is un-bypassed. Field
*69 applies.
*
73 AC RESTORE REPORT CODE |
This is sent when AC has been restored.
*
74 LOW BAT RESTORE REPORT CODE |
This is sent when a system low battery condition has been restored.
MISCELLANEOUS
OPTIONS
(
*
76 - *86)
*76 WATERFLOW ALARM SILENCING
Enter 0 for Manual Silence only (default); enter 1 for automatic
silence when waterflow ceases, provided no other fire alarms are
present.
The automatic silence option can only be used with the permission of
the local AHJ.
*77 ALARM BELL SOUND
Enter 0 for pulsing (default); enter 1 for steady
NOTE: The "pulsing" option causes the bell to sound using the NFPA
Three Tone Temporal Pattern
*78 ZONE TYPES 17 and 18 DELAY |
Enter 00-99 seconds (default = 00)
Note: You must enable the Delay for Zone Type 18 in field *57.
The combined sensor and program field *78 must not exceed 90
seconds.
*79 MAIN/BACKUP DIALER ENABLE |
Enter 0 to disable; enter 1 to enable (default= 1,1) M B
*82
CUSTOM ALPHA EDITING
May also be entered from the interactive program field *56. See the
Section on ALPHA DESCRIPTION PROGRAMMING for procedures.
*84 MISCELLANEOUS REPORT CODES
| | |
FIRE WALK FIRE WALK OFF-NORMAL
TEST START TEST END DIALER TEST
Enter 2 hex digits for each. (Default for each = 0)
Seitenansicht 53