
– 32 –
4) Enter the calculated
subtotals of all listed
outputs then add to get
combined current.
COMBINED AUX. POWER, BELL AND RELAY OUTPUT Total Current
Standby Alarm
Aux. Power Output Subtotal
Bell Output Subtotal XXXXX
Aux. Relay Output Subtotal
Add all subtotals
(Cannot exceed 350mA max. standby; 1.0 amp max. alarm)
5) These values are fixed.
5110XM PCB CURRENT Total Current
Standby Alarm
Includes 2-wire smoke detector and LED indicator PCB currents 155mA 235mA
6) Enter the calculated
combined currents then
add to total PCB
current.
TOTAL CONTROL LOAD Total Current
Standby Alarm
Combined aux. power, bell and aux. relay output current
Total PCB current 155mA 235mA
Total power supply load*
* Limit the total power supply standby current to 210 mA when a 60 hr. standby time is
desired.
7) Using the total
calculated power supply
load (step 6), calculate
the battery capacity
required for the
installation.
BATTERY CAPACITY CALCULATION WORKSHEET
(For 24 or 60 hour standby followed by 5 minute fire alarm)
Capacity Formula Calc Value
Standby Capacity total standby load X 24 or 60 hours X 1.1 contingency
factor (use total standby load from previous worksheet)
Alarm Capacity total alarm load X 0.083 hours (5 minutes)
(use total alarm load from previous worksheet)
Total Capacity Add standby and alarm capacities (14AH max)
8) Using the battery
capacity from step 7,
select the appropriate
battery.
BATTERY SELECTION TABLE
7 AH Yuasa NP7-12
14 AH Yuasa NP7-12 (connect 2 in parallel, mounted
vertically in cabinet)
Making the Battery Connections
1. Use the battery capacity calculation worksheet(above) to determine the
appropriate battery for the installation.
Do not connect the batteries until all devices have been wired to the control.
2. Verify that the proper float charging voltage (13.5–13.8VDC) is present
across the battery terminals of the 5110XM PCB. If not, check that the
auxiliary power and auxiliary relay outputs are not loaded in excess of their
ratings.
Kommentare zu diesen Handbüchern