– 42 –
Where:
SSS or SSSS = Subscriber ID
A = Alarm Code–1st digit Gg = Test Code (1st & 2nd digits)
Z = Typically Zone Number*–2nd digit G
O
G
O2
= Off Nornal Test Code (1st & 2nd digits)
Tt = Trouble Code (1st & 2nd digits) W
S
W
S2
= Walk Test Start (1st & 2nd digits)
S
P
S
P2
= Supervisory Code (1st & 2nd digits) W
E
W
E2
= Walk Test End (1st & 2nd digits)
Bb = Bypass Code (1st & 2nd digits) R = Restore Code (Alarm)
EA
C =
AC Loss Code (1st & 2nd digits) R
S
R
S2 = Restore Code (Supv) 1st & 2nd digits
LL
B =
Low Battery Code(1st & 2nd digits) R
T
t = Restore Code (Trbl)1st & 2nd digits
R
B
b = Restore Code (Byps)1st & 2nd digits
R
A
A
C
= Restore Code (AC)1st & 2nd digits
R
L
L
B =
Restore Code (Bat)1st & 2nd digits
*Zone numbers for: [*] & [#], or [B] = 07 [1] + [*], or [A] = 95
[3] + [#], or [C] = 96
Ademco Contact ID Reporting takes the following format:
CCCC Q EEE GG ZZZ
where: CCCC = Customer (subscriber) ID
Q = Event qualifier, where:
E = new event , and R = restore
EEE = Event code (3 hexadecimal digits)
Note: For a complete list of event codes, refer to the
central office receiver manual.
GG = Always 00
ZZZ = Zone/contact ID number reporting the alarm. System
status messages (AC Loss, Walk Test, etc.) contain
zeroes in the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
Code Definition
110 Fire Alarm Without Verification
111 Smoke Alarm With Verification
113 Waterflow Alarm
122 Silent Panic
123 Audible Panic
150 24 Hour Auxiliary
200 Fire Supervisory
301 AC Power
302 Low System Battery/Battery Test Fail
310 Ground Fault
321 Bell Trouble
351 Main Dialer Trouble
Code Definition
352 Backup Dialer Trouble
353 LORRA Trouble
373 Fire Zone Trouble
380 Trouble (global)
521 Bell Bypass
524 Auxiliary Relay Bypass
551 Main/Backup Dialer Bypass
570 Zone Bypass
602 Normal Dialer Test
607 Fire Walk Test
608 Off-Normal Dialer Test
Kommentare zu diesen Handbüchern