CAUTION: In mixed systems, the different amplifier configurations must be installed in different zone groups. It is not possible
to mix different amplifier configurations within the same zone group.
Maximum amplifier and speaker capacity for each zone group and the total system is shown in Table 7.
Table 7:
Maximum Amplifier and Speaker Capability
Maximum Capacity
Amplifier Configuration Total System Each Zone Group
Central Amplifier(s)
300W @ 100V
250W @ 70V
100W @ 25V
100W @ 100V
70W @ 70V
25W @ 25V
(See Note 1)
Zone Amplifiers or
Speaker-Amplifiers
150 Amplifier
Inputs
75 Amplifier
Inputs
(See Note 2)
NOTES:
1. The Zone Control can switch an audio input from a central amplifier of up to 300W @ 100V, 250W @ 70V, or 100W @
25V. This TOTAL SYSTEM
audio input can be distributed among the zone groups provided no single zone group
exceeds:
(A) 100W @ 100V, leaving 200W for the remaining system groups.
- or -
(B) 70W @ 70V, leaving 180W for the remaining system groups.
- or -
(C) 25W @ 25V, leaving 75W for the remaining groups.
2. The Zone Control can switch its preamplifier audio output to the 600 ohm inputs of up to 150 zone amplifiers or speaker-
amplifiers. This TOTAL SYSTEM
audio output can be distributed among the zone groups provided no SINGLE ZONE
exceeds 25 amplifier inputs, which would leave 125 amplifier inputs for the remaining zones.