FREQUENTLY ASKED TECHNICAL QUESTIONS
NUMBER
QUESTION ANSWER
11 "How do I hook up the NS4 separating the horn
and strobe while using the DSM Module and have
the horns do a Code 3 Pattern?"
Connect a NAC Circuit from the FACP to the Audible
Terminals of the DSM. Jumper from the Audible Terminals
to Input 1. Connect the Strobe portion of the NS4 to output
1 of the DSM. Connect the Horn portion of the NS4 to a
separate NAC Circuit from the FACP. Have the FACP
provide the Code 3 Pattern.
12 "How do I set either the NS or the AS appliances
for continuous horn operation?"
Remove the factory installed jumper from the Code 3
position. Note that you cannot get continuous horn when
connected to a sync module.
13 "I have the CH 70 Chime Strobe and I want to use
it with a Sync /module."
Wire the strobe portion of the Chime Strobe through the
Sync Module. Wire the Chime portion through your FACP
on a separate NAC Circuit and set the Chime to single
stroke and pulse the NAC Circuit.
14 "How do I set the DIP switches for Code 3 on a
MT-12/24-R?"
Look at the SW1 switch. Set positions 2 & 3 to the up
position and position 4 to the down position.
15 "How do I set the priorities on the AMT
appliance?"
By setting the SW 1 DIP switch. Position 1 sets the dB
level from either high or low. Positions 2 through 4 sets the
priorities of the signal.
16 "What kind of Back Box do I need to mount a bell
outdoors?"
The correct box to use is a WBB-R.
17 "What kind of Back Box do I need for the Series
E70 & ET70 Speakers when I need to mount the
a
liance on the surface?"
The correct box to use is the SBB-R for Red or the
SBB-W for White.
18 "How do I increase the output of the
STH-15S-R?"
Remove the cover plate on the side of the horn and adjust
the tap setting using a flat head screwdriver.
19 "On the new Mini Horn (MIZ-24TC-R), how do I set
the appliance for Code 3?"
There is a jumper plug on the rear of the appliance. Set the
plug so the plug is on the left pin.